Circuit breaker, ComPacT NSX100F, 36kA/415VAC, 4 poles 4D (neutral fully protected), TMD trip unit 100A
Manufacturer: Schneider Electric
Device short name: NSX100F
Poles description: 4P
Protected poles description: 4D
[In] rated current: 100A at 40°C
Performance level: F 36kA 415V AC
Trip unit name: TM-D
C10F4TM100 Unique to this line is the inclusion of two pre-installed base-mounted auxiliary contacts on the 40-80 AMP contactors. This innovative feature significantly reduces the need for additional auxiliary components, leading to a more compact and straightforward design. With a unified frame size across the LC1D40 to LC1D80 range, these contactors are an excellent choice for applications where space is limitedThe ComPacT NSX100F is a 4P 4d fixed circuit breaker with a remarkable breaking capacity of 36kA rms at 415VAC 50/60Hz. Operating seamlessly at 690VAC 50/60Hz, it incorporates a 100A rating thermal-magnetic trip unit (TMD) for adjustable thermal overload protection and fixed magnetic protection. With dimensions of 140mm x 161mm x 86mm, this compact circuit breaker offers optional functions and accessories, making it suitable for a wide range of applications. Compliant with international standards such as IEC 60947, CCC, EAC, and marine specifications, it seamlessly integrates into the Schneider Electric EcoStruxure Power architecture, enhancing the overall efficiency and reliability of power systems.
Main
Product name | ComPacT NSX new generation |
Device short name | NSX100F |
Product or component type | Circuit breaker |
Device application | Distribution |
Poles description | 4P |
Protected poles description | 4D |
[In] rated current | 100 A at 40 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
[Icu] rated ultimate short-circuit breaking capacity |
85 kA Icu at 220/240 V AC 50/60 Hz IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz IEC 60947-2
35 kA Icu at 440 V AC 50/60 Hz IEC 60947-2
25 kA Icu at 500 V AC 50/60 Hz IEC 60947-2
22 kA Icu at 525 V AC 50/60 Hz IEC 60947-2
8 kA Icu at 660/690 V AC 50/60 Hz IEC 60947-2
|
Performance level | F 36 kA 415 V AC |
Trip unit name | TM-D |