Kaʻa kaʻa kaʻa, TeSys Deca, 3P, 24 a 32A, mākēneki wela, nā pahu hoʻopaʻa wiliwili, ʻauʻau wili.
Mea hana: ʻO Schneider Electric
[Ma] helu ʻia i kēia manawa: 32A
hiki ke haki: 50 kA Icu at 400/415 V AC 50/60 Hz IEC 60947-2
ʻO ka moku kaʻa kaʻa ʻo TeSys GV, helu ʻia ma 32A/690V a hoʻolālā ʻia no nā noi kaʻa 3-phase a hiki i 15kW@400V, e hōʻike ana i kahi hoʻonohonoho 3-pole (3P). Hāʻawi ia i ka palekana thermal-magnetic hilinaʻi me kahi pae hoʻonohonoho wela o 24-32A a me ka tripping magnetic ma 13 mau manawa o ka manawa nominal (13xIn). He kiʻekiʻe ka haʻihaʻi ʻana o ka hāmeʻa o 50kA@400V. Hana ʻia nā hoʻokuʻi ʻana ma o nā ʻōkuhi screw clamp. Loaʻa iā ia kahi puʻupuʻu rotary no ka mana hoʻomaka-hoʻomaha, i hōʻoia ʻia no 100,000 mau kaʻina ma lalo o nā kūlana AC-3. Ua hōʻoia ʻia kēia mea haʻihaʻi kaapuni e nā kūlana honua lehulehu (IEC, UL, CSA, CCC, EAC, Marine, ATEX) a ua kūpaʻa ʻo Green Premium, e hui ana i nā kuhikuhi RoHS a me REACh.
Nui
| inoa huahana | TeSys GV2 |
| ʻAno huahana a mea ʻāpana paha | Kaʻa kaʻa kaapuni |
| inoa pōkole mea hana | GV2P |
| Noi Mea Hana | Pale kaʻa |
| ʻenehana hui huakaʻi | Thermal-magnetic |
| ʻO ka wehewehe ʻana i nā pou | 3P |
| ʻano hoʻoponopono | 35 mm kaila DIN symmetrical: ʻoki ʻia Panel: wili (me 2 x M4 wili) |
| Ka mana kaʻa kW | 15 kW ma 400/415 V AC 50/60 Hz 18.5 kW ma 500 V AC 50/60 Hz 22 kW ma 690 V AC 50/60 Hz |
| hiki ke haki | 100 kA Icu ma 230/240 V AC 50/60 Hz e like me IEC 60947-2 50 kA Icu ma 400/415 V AC 50/60 Hz e like me IEC 60947-2 20 kA Icu ma 440 V AC 50/60 Hz e like me IEC 60947-2 10 kA Icu ma 500 V AC 50/60 Hz e like me IEC 60947-2 4 kA Icu ma 690 V AC 50/60 Hz e like me IEC 60947-2 |