Circuit breaker ComPacT NSX160F, 36kA at 415VAC, TMD trip unit 160A, 3 poles 3d C25F3TM160
Manufacturer: Schneider Electric
Device short name: NSX100H
Poles description: 3P
Protected poles description: 3D
[In] rated current: 160 A at 40 °C
Performance level: F 36kA 415V AC
Trip unit name: TM-D
The ComPacT NSX250F is a comprehensive 3-pole, 3-phase fixed circuit breaker designed to optimize space and enhance breaking capacity. It is an ideal solution for a wide range of standard and specialized applications. With a breaking capacity (Icu) of 36kA rms at 415VAC 50/60Hz and an operational voltage of 690VAC 50/60Hz, this breaker offers robust performance.
The NSX250F features a 160A-rated thermal-magnetic trip unit (TMD) that provides adjustable thermal overload protection and fixed magnetic protection. This 3-pole version, measuring 105mm x 161mm x 86mm, comes with a variety of optional functions and accessories to suit your specific needs.
Compliant with international standards such as IEC 60947, CCC, EAC, and marine specifications, the ComPacT NSX250F ensures reliability and versatility. Additionally, it is an integral part of Schneider Electric's EcoStruxure Power architecture, allowing for seamless integration into your power management system.
Main
| Product name | ComPacT NSX new generation |
| Device short name | NSX100H |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3D |
| [In] rated current | 160 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| [Icu] rated ultimate short-circuit breaking capacity | 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 480 V AC 50/60 Hz conforming to UL 508
|
| Performance level | F 36 kA 415 V AC |
| Trip unit name | TM-D |